PORTUNUS (4/0) – ALUMINUM TRIPLEX SERVICE DROP – AAC NEUTRAL MESSANGER

Triplex Service Drop Aluminum Conductor cable is designed for use to supply power from utility lines to the consumer weather head. For service at 600 volts or lower (phase to phase) at a conductor temperature of 90°C maximum for cross linked insulation or 75°C maximum for polyethylene insulation.

APPLICATION

Triplex Service Drop Aluminum Conductor cable is designed for use to supply power from utility lines to the consumer weather head. For service at 600 volts or lower (phase to phase) at a conductor temperature of 90°C maximum for cross linked insulation or 75°C maximum for polyethylene insulation.

CODE WORD

Portunus

STANDARDS

ASTM B-230 Aluminum 1350–H19 Wire for Electrical Purposes • ASTM B-231 Concentric-Lay-Stranded Aluminum 1350 Conductors • ASTM B-232 Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR) • ASTM B-399 Concentric-Lay-Stranded Aluminum-Alloy 6201-T81 Conductors • ICEA S-76-474 Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600 Volts • RUS Accepted

INSULATION

Black cross linked polyethylene (XLP) insulation. Polyethylene (PE) insulation is available upon request.

CONDUCTORS

Concentric strand or compressed 1350-H19 series aluminum conductor

MESSANGER

Concentric strand AAC, 6201 alloy, or ACSR bare neutral messenger

PHASE CONDUCTORS SIZE (AWG/kcmil)

4/0

PHASE CONDUCTORS STRAND

19/w

PHASE CONDUCTORS INSULATION THICKNESS (INCHES)

0,06

BARE NEUTRAL MESSENGER SIZE (AWG/KCMIL)

4/0

BARE NEUTRAL MESSENGER STRAND

19

BARE NEUTRAL MESSENGER BREAKING STRENGTH (LBS)

4 020

COMPLETED CABLE DIAMETER (INCHES)

1,35

COMPLETED CABLE XLP WEIGHT (LBS/KFT)

693

COMPLETED CABLE POLY WEIGHT (LBS/KFT)

684

AMPACITY ** XLP 90°C (AMPS)

315

AMPACITY ** POLY 75°C (AMPS)

245

Premium Wire & Cable Materials for Longevity & Durability

Premium Wire & Cable Materials for Longevity & Durability

Get the products you can trust: Tested & Certified.