MONMOUTH (4/0) – Triplex Aluminum 8000 Series Conductor 600V URD

Aluminum 8000 Series 600V URD cable is designed for use in secondary distribution circuits, where installed in duct or direct burial applications, where increased flexibility is needed. The conductors are rated Type RHH/RHW-2 or USE-2. Maximum operating temperature is not to exceed 90°C in wet and dry locations. Voltage rating is 600 volts. As an option, this cable can be provided pre-pulled into duct.

APPLICATION

Aluminum 8000 Series 600V URD cable is designed for use in secondary distribution circuits, where installed in duct or direct burial applications, where increased flexibility is needed. The conductors are rated Type RHH/RHW-2 or USE-2. Maximum operating temperature is not to exceed 90°C in wet and dry locations. Voltage rating is 600 volts. As an option, this cable can be provided pre-pulled into duct.

CODE WORD

Monmouth

STANDARDS

UL 44 Thermoset-Insulated Wires and Cables • UL 854 Service-Entrance Cables • ASTM B800 8000 Series Aluminum Alloy Wire for electrical Purposes-Annealed and Intermediate Tempers • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation • ASTM B901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction • ICEA S-105-692 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables • Federal Specification A-A-59544A Cable and Wire, Electrical • RUS Accepted

INSULATION

Phase Conductors – Black sunlight resistant cross-linked polyethylene (XLP) insulation • Neutral Conductors – Black XLP with 3 extruded yellow stripes

CONDUCTORS

• Compact bare AA-8000 series aluminum alloy, Class B stranded per ASTM

ASSEMBLY

Two phase conductors and the neutral are cabled together, with surface printing for identification. The neutral conductor has a yellow stripe and sequential footage markings.

PHASE CONDUCTORS SIZE (AWG/kcmil)

4/0

PHASE CONDUCTORS NO. OF STRANDS

19

PHASE CONDUCTORS INSULATION THICKNESS (INCHES)

0,08

NEUTRAL SIZE (AWG/KCMIL)

4/0

NEUTRAL NO. OF STRAND

19

NEUTRAL INSULATION THICKNESS (INCHES)

0,08

DIAMETER SINGLE PHASE CONDUCTOR (INCHES)

1,42

DIAMETER COMPLETE CABLE (INCHES)

1,42

WEIGHT (LBS/KFT)

826

AMPACITY DIRECT BURIAL (AMPS)

315

AMPACITY - IN DUCT (AMPS)

240