4 x 250 MCM – Aluminum Service Entrance Cable with Bare Ground – Type SE Style R (SER)

Aluminum SER cable is primarily used as panel feeder in multiple unit dwellings and for branch circuits. Maximum operating temperature is not to exceed 90°C in wet or dry locations. Voltage rating is 600 volts.

APPLICATION

Aluminum SER cable is primarily used as panel feeder in multiple unit dwellings and for branch circuits. Maximum operating temperature is not to exceed 90°C in wet or dry locations. Voltage rating is 600 volts.

PART NUMBER

250-04ALUMG-R-SER

STANDARDS

UL 44: Thermoset-Insulated Wires and Cables • UL 854: Standard for Service-Entrance Cables • ASTM B-258, B-800, B-801 • National Electric Code

JACKET COLOR

GRAY

CONDUCTORS

8003 series aluminum alloy, solid or compact stranded

JACKET

Gray sunlight resistant polyvinyl chloride (PVC) jacket

INSULATION

Type XHHW-2 cross-linked polyethylene (XLPE) insulation.

COLOR CODE

Black, White, Red & Blue

ASSEMBLY

Four insulated conductors and a bare ground conductor cabled together and covered with a reinforced binder tape

INSULATED CONDUCTOR - SIZE (AWG/KCMIL)

4 x 250

INSULATED CONDUCTOR - NUMBER OF STRANDS

22

BARE CONDUCTOR - SIZE (AWG/KCMIL)

3/0

BARE CONDUCTOR - NUMBER OF STRANDS

22

NOMINAL OD - INCHES

1,85

NOMINAL OD - MM

46,99

NET WEIGHT (LBS/KFT)

1585

ALLOWABLE AMPACITIES 75°C

205

ALLOWABLE AMPACITIES 90°C

230

ALLOWABLE AMPACITIES DWELLING

225

Premium Wire & Cable Materials for Longevity & Durability

Premium Wire & Cable Materials for Longevity & Durability

Get the products you can trust: Tested & Certified.