3 x 300 MCM – Aluminum Service Entrance Cable with Bare Ground – Type SE Style R (SER)

Aluminum SER cable is primarily used as panel feeder in multiple unit dwellings and for branch circuits. Maximum operating temperature is not to exceed 90°C in wet or dry locations. Voltage rating is 600 volts.

APPLICATION

Aluminum SER cable is primarily used as panel feeder in multiple unit dwellings and for branch circuits. Maximum operating temperature is not to exceed 90°C in wet or dry locations. Voltage rating is 600 volts.

PART NUMBER

BWC-300-03ALUMG-R-SER

STANDARDS

UL 44: Thermoset-Insulated Wires and Cables • UL 854: Standard for Service-Entrance Cables • ASTM B-258, B-800, B-801 • National Electric Code

JACKET COLOR

GRAY

CONDUCTORS

8011 series aluminum alloy, solid or compact stranded

JACKET

Gray sunlight resistant polyvinyl chloride (PVC) jacket

INSULATION

Type XHHW-2 cross-linked polyethylene (XLPE) insulation.

COLOR CODE

Black, White & Red

ASSEMBLY

Three insulated conductors and a bare ground conductor cabled together and covered with a reinforced binder tape

INSULATED CONDUCTOR - SIZE (AWG/KCMIL)

3 x 300

INSULATED CONDUCTOR - NUMBER OF STRANDS

35

BARE CONDUCTOR - SIZE (AWG/KCMIL)

4/0

BARE CONDUCTOR - NUMBER OF STRANDS

18

NOMINAL OD - INCHES

1,65

NOMINAL OD - MM

41,91

NET WEIGHT (LBS/KFT)

1347

ALLOWABLE AMPACITIES 75°C

230

ALLOWABLE AMPACITIES 90°C

260

ALLOWABLE AMPACITIES DWELLING

250