22 AWG 3 C PLENUM SHIELDED – BLUE (JOHNSON CONTROLS)

22 AWG 3 conductors 7 strands bare copper wire, plenum rated PVC insulation, shielded, and an overall plenum rated PVC jacket

APPLICATION

22 AWG 3 conductors 7 strands bare copper wire, plenum rated PVC insulation, shielded, and an overall plenum rated PVC jacket

PART NUMBER

4420PL-BLU-JCI

STANDARDS

• Suitable for installation under NEC (NFPA 70) articles 800, 725 and 760 guidelines
• Suitable for installation in Canada under Section 60 of CEC, Part I
• C(UL)US listed as CMP per UL standard 444 and per CSA C22.2 No. 214-17
• UL listed as CL3P per UL standard 13 or FPLP per UL standard 1424
• Meets NFPA 262 (Steiner tunnel) flame test
• Meets RoHS 2002/95/EC Directive, RoHS 2 2011/65/EU Directive, RoHS 3 2015/863/EU Directive
• REACH compliant per Regulation (EC) No 1907/2006 (224) Updated June 10, 2022
• Operating Voltage: 300V RMS
• Made in the USA

JACKET COLORS

BLUE

JACKET

Plenum Rated Polyvinylchloride

CONDUCTORS

22 AWG 7 STRANDS; ANNEALED BARE COPPER

COLOR CODE

BLACK, BLUE, WHITE

INSULATION

PLENUM RATED POLYVINYLCHLORIDE

ASSEMBLY

SHIELDED; ALUMINUM MYLAR TAPE – 100% COVERAGE WITH 24 AWG 7 STRAND TINNED COPPER

RIPCORD

YES

AWG

22

CONDUCTOR

3

STRANDING

7

NOMINAL LAY LENGTH (LHL - INCHES)

3

INSULATION THICKNESS (INCHES)

0,007

JACKET WALL THICKNESS (INCHES)

0,015

OVERAL DIAMETER (INCHES)

.122 ± .010

NET WEIGHT

14

VOLTAGE

300

Premium Wire & Cable Materials for Longevity & Durability

Premium Wire & Cable Materials for Longevity & Durability

Get the products you can trust: Tested & Certified.