2/0 – Aluminum RHH/RHW-2/USE-2 600V 90°C XLP Insulation

USE-2 cables are primarily used for power distribution, in raceways in accordance with National Electrical Code, except that the cable is not rated for use in cable tray. USE2 is approved for direct burial and for service entrance below ground. USE-2 cables may be used in wet or dry locations, with conductor temperatures not exceeding 90°C. Voltage rating for USE-2 cable is 600V.

APPLICATION

USE-2 cables are primarily used for power distribution, in raceways in accordance with National Electrical Code, except that the cable is not rated for use in cable tray. USE2 is approved for direct burial and for service entrance below ground. USE-2 cables may be used in wet or dry locations, with conductor temperatures not exceeding 90°C. Voltage rating for USE-2 cable is 600V.

PART NUMBER

BWC-2/0-01XL-USE-2-ALUM

STANDARDS

UL 44 • UL 854 • NEMA WC 70/ICEA S-95-658 • Requirements of the National Electrical Code • ASTM B800, B801, B836 • Sunlight resistant • RUS ACCEPTED

CONDUCTORS

Compact bare 8000 series aluminum, with Class B stranding per ASTM

INSULATION

Abrasion, heat and moisture resistant cross-linked polyethylene insulation (XLP)

CONDUCTOR SIZE (AWG/KCMIL)

2/0

CONDUCTOR DIAMTER (INCHES)

0,378

CONDUCTOR DIAMETER (MM)

9,6

INSULATION THICKNESS (INCHES)

0,08

INSULATION THICKNESS (MM)

2,03

OVERALL DIAMETER (INCHES)

0,539

OVERALL DIAMETER (MM)

13,69

NET WEIGHT (LBS/KFT)

182

AMPACITY AT 90°C

150