12 AWG 2 C METAL CLAD W/OVERALL JACKET & GROUND – THHN/THWN Conductors/Aluminum Armor

Jacketed MC Cable is suitable for use in branch, feeder and distribution circuits in commercial, industrial, institutional and multi-residential applications. The cable is approved for power, lighting, control and signal circuits. Suitable for use in cable tray and other approved raceways and can be exposed or concealed. The cable can be used in places of assembly of 100 people or more, such as studios and theaters. Voltage ratings should not exceed 600V in any applications. NOTE: Priority Wire & Cable’s MC Cable with copper conductor is suitable for use in vertical applications if installed per the requirements of the NEC as detailed in section 300.19, table 300.19(A) and section 330.30.

APPLICATION

Jacketed MC Cable is suitable for use in branch, feeder and distribution circuits in commercial, industrial, institutional and multi-residential applications. The cable is approved for power, lighting, control and signal circuits. Suitable for use in cable tray and other approved raceways and can be exposed or concealed. The cable can be used in places of assembly of 100 people or more, such as studios and theaters. Voltage ratings should not exceed 600V in any applications. NOTE: Priority Wire & Cable’s MC Cable with copper conductor is suitable for use in vertical applications if installed per the requirements of the NEC as detailed in section 300.19, table 300.19(A) and section 330.30.

PART NUMBER

BWC-12-02MCA/JKT

STANDARDS

ASTM B3, B8, B258 • UL standards 83, 1569 • UL listed for sunlight resistant, for cable tray use, and for direct burial in earth or concrete • IEEE 1202 vertical tray flame test (70,000 BTU/hr.) • NEC Articles 230.43, 300.22, 330, 518.4, 520.5, 530, 545.4 & 645 • Class I Div. 2, Class II Div. 2 and Class III Div. 1 Div. 2 for hazardous locations • Federal Specification A-A-59544

CONDUCTORS

Solid or stranded soft drawn bare copper insulated with moisture and flame resistant PVC/nylon insulation rated THHN/THWN, 90°C dry and 75°C wet

ASSEMBLY

• Insulated conductors and ground conductor cabled together with a Mylar tape

GROUND

Insulated with green PVC/nylon rated THHN/THWN

COLOR CODE

120/280V – 2 CONDUCTORS (WHITE, BLACK); 3 CONDUCTORS (WHITE, BLACK, RED); 4 CONDUCTORS (WHITE, BLACK, RED, BLUE)

ARMOR

Aluminum interlocked tape armor applied over the cable assembly

Premium Wire & Cable Materials for Longevity & Durability

Premium Wire & Cable Materials for Longevity & Durability

Get the products you can trust: Tested & Certified.