16 AWG 1 TRIAD ALUMINUM INTERLOCKING ARMOR (AIA) INSTRUMENTATION CABLE

XLPE/AIA/PVC 600V Instrumentation Cables provide an excellent crush resistance and a cost effective alternative to installations in conduit as well as being Sunlight, Oil and Chemical resistant. They are suitable for control, instrumentation and process control circuits, where protection against electrostatic interference from both outside of the cable and from pair to pair is needed. The cables are suitable for wet or dry applications, direct burial, indoor or outdoor locations, installed in cable trays, ducts, aerially or conduits and for applications up to 600 volt and temperatures up to 90°C. The cables are suitable for use in Class 1 Division 2 Hazardous locations per NEC.

APPLICATION

XLPE/AIA/PVC 600V Instrumentation Cables provide an excellent crush resistance and a cost effective alternative to installations in conduit as well as being Sunlight, Oil and Chemical resistant. They are suitable for control, instrumentation and process control circuits, where protection against electrostatic interference from both outside of the cable and from pair to pair is needed. The cables are suitable for wet or dry applications, direct burial, indoor or outdoor locations, installed in cable trays, ducts, aerially or conduits and for applications up to 600 volt and temperatures up to 90°C. The cables are suitable for use in Class 1 Division 2 Hazardous locations per NEC.

PART NUMBER

BWC-16-01TRAIA-OS

STANDARDS

UL Type MC • IEEE 1202/UL 1581 (FT-4) 70,000 BTU/hr Flame Test • ICEA T-29-520 210,000 BTU/hr Flame Test • ICEA S-73-532, where applicable • Meets cold bend test at -40°C

OUTER JACKET

Flame and sunlight resistant Polyvinyl Chloride (PVC), black, with ripcord

CONDUCTORS

Fully annealed bare copper Class B compressed strand per ASTM Standards

INSULATION

Cross-linked Polyethylene (XLPE)

INNER JACKET

Polyvinyl Chloride (PVC), black

COLOR CODE

Pairs: Black and White Numbered • Triads: Black, White and Red Numbered

ARMOR

Aluminum Interlocked Armor (AIA)

Shield

FFE Aluminum/Mylar Tape with 100% coverage on each pair or triad, with an overall Aluminum/Mylar Tape with 100% coverage with a stranded tinned copper drain wire in contact with all shields

OUTER DRAIN WIRE (AWG)

16

OUTER DRAIN WIRE (STRAND)

7

NO. OF TRIADS

1

INSULATION THICKNESS (INCHES)

0,03

INNER JACKET THICKNESS (INCHES)

0,04

INNER JACKET THICKNESS (MM)

1,02

OUTER JACKET THICKNESS (MM)

1,27

OVERALL DIAMETER (INCHES)

0,661

OVERALL DIAMETER (MM)

16,79

NET WEIGHT (LBS/KFT)

205

Premium Wire & Cable Materials for Longevity & Durability

Premium Wire & Cable Materials for Longevity & Durability

Get the products you can trust: Tested & Certified.